About the APC Symmetra LX Main Intelligence Module SYMIM5 - Refurbished
Model
SYMIM5
Includes
(1) SYMIM5 Module
Warranty
1 year full replacement warranty included, additional warranty is available
How to Install the SYMIM5 Main Intelligence Module
When replacing both intelligence modules in any single phase Symmetra UPS, the user should never remove both intelligence modules at the same time even with the UPS in Maintenance Bypass. Removing both modules at the same time prohibits the replacement modules from copying the existing settings of the UPS system. This could result in undesired operation of the UPS or inappropriate power being supplied to the load. Please adhere to the following procedures when replacing intelligence modules in any Symmetra UPS system.If one intelligence module requires replacement:1) On most Symmetra systems, the Powerview LCD display connects to one of the intelligence modules via a cat5 UTP patch cable. This cable should be disconnected from the intelligence module to which the display connects. If the UPS being serviced is a Symmetra Power Array (Masterframe or Miniframe) this will not be necessary as the Powerview display does not directly connect to either intelligence module.2) If, for some reason, there is only one intelligence module installed, the UPS must be placed into the maintenance bypass mode of operation prior to removing this single intelligence module. This should be done by closing the breaker marked maintenance bypass. Depending on which Symmetra UPS is being serviced, the location of this breaker will vary. If there are two intelligence modules, it is not necessary to place the UPS in bypass.
If both intelligence modules require replacement
1) On most Symmetra systems, the Powerview LCD display connects to one of the intelligence modules via a category 5 unshielded twisted pair patch cable. This cable should be disconnected from the intelligence module to which it connects in order to ease the process of installation. If the UPS is a Symmetra Power Array (Masterframe or Miniframe) this will not be necessary as the Powerview display does not directly connect to either intelligence module.2) Remove the intelligence module that is not in control.Symmetra LX will indicate which intelligence module is in control by illuminating an additional green LED on the far left of the LED array. Symmetra Power Array and Symmetra RM indicate which module is in control using the redundant intelligence module's orange LED (second LED from the left on the LED array). If this LED is illuminated, the redundant intelligence module is in control. If this LED is not illuminated, the main intelligence module is in control.3) Insert the replacement intelligence module in the now empty bay. Allow this module several seconds to boot up and confirm that the module is operating properly by the LEDs illuminated on the intelligence module. The green LED to the far right of the module's LED array should be solid. If the red fault LED on the intelligence module illuminates and stays lit, there is a fault. Please contact APC support.4) Remove the remaining intelligence module and insert the second replacement module. Allow this module to boot up and confirm that the module is booted by the LEDs present on the module. The green LED to the far right of the module's LED array should be solid. If the red fault LED on the intelligence module illuminates and stays lit, there is a fault. Please contact APC support.5) Ensure that the main intelligence module has assumed control of the UPS.
Model Description: APC Symmetra LX Main Intelligence Module
Compatibility: Select APC Symmetra UPS Systems (check the Part Number on your intelligence module to make sure you get the right one)
Condition: Refurbished Intelligence Module (1 Year Warranty included, additional warranty available)
Symmetra LX will indicate which intelligence module is in control by illuminating an additional green LED on the far left of the LED array. By default, the bottom intelligence module will take control. Symmetra Power Array and Symmetra RM indicate which module is in control using the redundant intelligence module's orange LED (second LED from the left on the LED array). If this LED is lit, the redundant intelligence module is in control. If this LED is extinguished, the main intelligence module is in control.6) If applicable, reconnect the Powerview display and wait for it to boot. Confirm that there are no faults present. If there are faults present, please contact support. Specifications for APC Symmetra SYMIM5 Intellignece Module:Physical:Maximum height1.63 inches (41 mm)Maximum width6.63 inches (168 mm)Maximum depth19.63 inches (499 mm) Net weight5.00 lbs. (2.27 kg)