Exact-fit UPS replacement batteries
Peak Energy PK12V40 12V 40Ah Battery
High Performance
Brand New Fresh Stock
1 Year Warranty Included
| Recharge Method | Connect battery to a Current Limited, Constant Voltage Source.Limit the initial recharge current to 10 Ah or less.To promote satisfactory performance in Cyclic applications, a minimum recharge current of 4 Ah is recommended.Employ Charge Voltage Temperature Compensation when battery temperature is less than 50°F (10°C) 0r greater than 86°F (30°C), Use the Recommended voltage and normalize to 77°F (25°C).The use of compensation through the whole temperature range is not generally necessary, but doing so may optimize service life.If the Recommended recharge voltage is used, no Temperature Compensation is required within the range of 50 ~ 86°F (10 ~ 30°C)Cyclic Application Recharge Voltage (77°F / 25°C)MinimumRecommendedMaximum |
| Temperature Coefficient | -2.8mV/°F/Cell (-5mV/°C/Cell)Standby Application Recharge Voltage (77°F/25°C)MinimumRecommendedMaximum |
| Temperature Coefficient | -1.7mV/°F/Cell (-3mV/°C/Cell) |